| Product type | Uninterrupted power supply; Online |
| Model | PM 2000E Online LCD |
| Capacity | 2000 VA / 1400W |
| Product type | Uninterrupted power supply; Online |
| Model | PM 2000E Online LCD |
| Capacity | 2000 VA / 1400W |
| Input | Phase: Single phase with ground |
| Frequency range: 46Hz – 54Hz / 54 – 64Hz | |
| Power factor: 0.7 | |
| Voltage range: Line low transfer 176VAC/140VAC/120VAC/110VAC (±5V) |
|
| Voltage range Line low comeback 186VAC/150VAC/130VAC/120VAC (±5V) |
|
| Voltage range Line high transfer 276VAC (±5V) |
|
| Voltage range Line high comeback 266VAC (±5V) |
|
| Output | Phase: Single |
| Voltage: 208VAC/220VAC/230VAC/240VAC | |
| Voltage regulation: ± 2 % | |
| Frequency (sychronized range): 46Hz – 56Hz / 54 – 64Hz | |
| Frequency (Batt. mode): 1 Hz/s | |
| Current crest ratio: 3:1 | |
| Harmonic distortion: ≦4% THD (Linear Load) |
|
| Harmonic distortion: ≦7% THD (Non-Linear Load) |
|
| Output waveform (Batt. mode): Pure sine wave | |
| Efficiency | To AC mode: 86% |
| To Battery mode: 83% | |
| Battery | Battery type: 12V / 7AH |
| Numbers of batteries: 4 | |
| Backup time (65% Load): >5minutes | |
| Recharge time: 5h charge to 90% | |
| Charging current (Max.): 1.0A | |
| Charging voltage: (54.6±0.6)VDC | |
| Transfer time | AC to DC: Zero |
| Inverter to bypass: 5ms(Typical) | |
| Indicator | Status(LED): Load Level / Battery Level / Battery Mode / AC Mode / Bypass Mode / Fault |
| Status(LCD): Load Level / Battery Level / Input / Output / Operating Mode Information |
|
| Audible alarm | Battery mode: Sounding every 4 seconds |
| Low battery: Sounding every second | |
| Overload: Sounding twice every second | |
| Fault: Continously sourding | |
| Physical | Dimension, D*W*H (mm): 369 * 190 * 318 |
| Net weight (kgs): 20 | |
| Environment | Operating environment: 0~40℃, 20~90% relative humidity (non-condensing) |
| Noise level: < 45dB @ 1 Meter | |
| Interface | Smart RS-232: Support WinPower software |
| SNMP (option): Power management from SNMP manager and web brower | |
| Accessories | IEC output cable x1 (for PM 1000E-3000E Online LCD only),RS-232 cable x1,application CD,user guide |